Genvex Optima 270 Modbus Register 1: T3 air intake
Technical documentation for Modbus register 1 on Genvex Optima 270. Data type: S WORD. Includes Python and YAML configuration examples.
January 16, 2026
•
1 min read
Technical Definition
The register T3 air intake at address 1 is used to monitor t3 air intake on the Genvex Optima 270.
- Protocol: Modbus RTU
- Data Type: S WORD
- Unit: °C
- Access: Read Only
How to Read (Python pymodbus)
Use this code snippet to read this specific value via RS485:
from pymodbus.client.sync import ModbusSerialClient
client = ModbusSerialClient(method='rtu', port='/dev/ttyUSB0', baudrate=9600)
client.connect()
# Read T3 air intake (Address: 1)
# Note: Check if your device uses 0-based or 1-based addressing
result = client.read_input_registers(address=1, count=2, unit=1)
if not result.isError():
print(f"Raw Value: {result.registers}")
else:
print("Error reading register")
client.close()
Integration (Home Assistant)
Paste this into your configuration.yaml:
- platform: modbus_controller
name: "T3 air intake"
address: 1
value_type: S_WORD
unit_of_measurement: "°C"
Connection Diagram
Here is the standard RS485 wiring for this configuration:
graph TD
PLC[Host Controller / Home Assistant]
Device[Genvex Optima 270]
PLC -- "A+ (D+)" --> Device
PLC -- "B- (D-)" --> Device
PLC -- GND --> Device
💡 Engineer's Insight
Analysis: Temperature of intake air in degrees Celsius (°C). Measured before air treatment.
Troubleshooting: 0 could mean a sensor fault or very low ambient Temperature. Check sensor and ventilation system status.